RESIDUAL CURRENT CIRCUIT BREAKERS
              WITH OVERCURRENT PROTECTION






                                                       JVL16 SERIES RCBO (10kA)

                                                       ■ Material of Housing : High quality PA66
                                                       ■ Residual Current Characteristics : AC, A
                                                       ■ Tripping Curve : B, C, D
                                                       ■ Rated Short-Circuit Capacity : 10kA
                                                       ■ Rated Residual Operating Current (mA) : 0.03, 0.1, 0.3
                                                       ■ Tripping Duration : Instantaneous≦0.1s
                                                       ■ Electro-Mechanical endurance : 4,000 cycles

                                  10kA           CB

                Model Type       Standard      Rated Current (A)     Poles (P)  Rated Voltage (V)  Breaking capacity


                                                   IJĭġijĭġĴĭġĵ
                                IEC61009,
                   JVL16                          ķĭġIJıĭġIJĴĭġIJķ      1P+N           AC 240V             10kA
                                GB16917.1        ijıĭġijĶĭġĴijĭġĵıł



                  Test                                                                Expected
               Procedure    Tripping type  Test Current  Initial State  Tripping Time   Result         Remark
                   A          B, C, D        1.13ln         cold          t≧1h        No Tripping
                                                                                                   Current in the 5s in
                   B          B, C, D        1.45ln    After test (A)     t<1h         Tripping      the increase of
                                                                                                        stability
                   C          B, C, D        2.55ln         cold       1s<t<60s        Tripping
                                 B            3ln
                                                                                                      Turn on the
                   D             C            5ln          Cold          t≧0.1s       No Tripping   auxiliary switch to
                                                                                                    close the current
                                 D            10ln
                                 B            5ln
                                                                                                      Turn on the
                   E             C            10ln          cold         t<0.1s        Tripping     auxiliary switch to
                                                                                                    close the current
                                 D            20ln
                    The terminology “cold state” refer to that no load is carried before testing at the reference setting temperature. .


                 Type        ln/A        l△△n/A   Residual Current (l△△) Is Corresponding To The Following Breaking Time (s)
                                                                             5A,10A,20A,50A,
                AC type    Any value   Any value   ln     2ln     5ln
                                                                             100A, 200A,500A
                 A type    Any value    >0.01     1.4ln  2.8ln    7ln
                                                   0.3    0.15   0.04             0.04              Max.Beak-Time
                            The general type RCBO whose current l△n is 0.03mA or less can use 0.25A instead of 5 l△n.