RESIDUAL CURRENT CIRCUIT BREAKERS
WITH OVERCURRENT PROTECTION
JVL16 SERIES RCBO (10kA)
■ Material of Housing : High quality PA66
■ Residual Current Characteristics : AC, A
■ Tripping Curve : B, C, D
■ Rated Short-Circuit Capacity : 10kA
■ Rated Residual Operating Current (mA) : 0.03, 0.1, 0.3
■ Tripping Duration : Instantaneous≦0.1s
■ Electro-Mechanical endurance : 4,000 cycles
10kA CB
Model Type Standard Rated Current (A) Poles (P) Rated Voltage (V) Breaking capacity
IJĭġijĭġĴĭġĵ
IEC61009,
JVL16 ķĭġIJıĭġIJĴĭġIJķ 1P+N AC 240V 10kA
GB16917.1 ijıĭġijĶĭġĴijĭġĵıł
Test Expected
Procedure Tripping type Test Current Initial State Tripping Time Result Remark
A B, C, D 1.13ln cold t≧1h No Tripping
Current in the 5s in
B B, C, D 1.45ln After test (A) t<1h Tripping the increase of
stability
C B, C, D 2.55ln cold 1s<t<60s Tripping
B 3ln
Turn on the
D C 5ln Cold t≧0.1s No Tripping auxiliary switch to
close the current
D 10ln
B 5ln
Turn on the
E C 10ln cold t<0.1s Tripping auxiliary switch to
close the current
D 20ln
The terminology “cold state” refer to that no load is carried before testing at the reference setting temperature. .
Type ln/A l△△n/A Residual Current (l△△) Is Corresponding To The Following Breaking Time (s)
5A,10A,20A,50A,
AC type Any value Any value ln 2ln 5ln
100A, 200A,500A
A type Any value >0.01 1.4ln 2.8ln 7ln
0.3 0.15 0.04 0.04 Max.Beak-Time
The general type RCBO whose current l△n is 0.03mA or less can use 0.25A instead of 5 l△n.