JVL16R SERIES RCCB
․ Material of Housing : High quality PA66
․ AC 230(240)/400(415)V ; 50/60Hz
․ Residual Current Characteristics : A, AC, G, S
․ Rated Condition Short-Circuit Current lnc: 10kA
․ Rated Conditional Residual Short-Circuit Current l△c: 10kA
․ Residual Tripping Current Range : 0.5 l△n~ l△n
․ Electro-Mechanical endurance : 4,000 cycles
10kA CB RoHS RoHS
Specification :
Model Type Standard Rated Current (A) Poles (P) Rated Voltage Breaking capacity
JVL16R IEC61008 25, 40, 63A 2P AC 230/400V 10kA
4P
Residual Current Action Breaking Time :
Residual Current (l△n) Is Corresponding To The Following Breaking Time (S)
type ln/A l△n/A 5A,10A,20A,50A,
l△n 2△n 5△n
100A,200A,500A
Any Any
General type 0.3 0.15 0.04 0.04 Max. Break-Time
value value
0.5 0.2 0.15 0.15 Max. Break-Time
S type ≧25 >0.03
0.13 0.06 0.05 0.04 Min Non-Driving Time
Any Any 0.5 0.2 0.15 0.15 Max. Break-Time
G type
value value 0.01 0.01 0.01 0.01 Min Non-Driving Time
Residual Current Operated Circuit Breaker Tripping Current Range :
type Tripping Current l△/A
AC 0.5l△n<l△<l△n
Lagging Angle l△n>0.01A l△n≦0.01A
0 0.35l△n ≦l△≦1.4 l△n 0.35l△n ≦l△≦2l△n
A
90 0.25l△n ≦l△≦1.4 l△n 0.25l△n ≦l△≦2l△n
135 0.11l△n ≦l△≦1.4 l△n 0.11l△n ≦l△≦2l△n
Overall & Installation Dimensions :
185