THERMAL


         OVERLOAD RELAYS




                                                T TYPE THERMAL RELAY


                                                The relay is suitable for using in the power circuits up to rated
                                                voltage 660V, rated current 500A 50Hz or 60Hz for overload and
                                                loss of phase protection of three phases induction motor and
                                                often combined with B series AC contactor into magnetic starter.
                                                T16 & T25 thermal relays have a friction trip operating
                                                mechanism with loss of phase running protection, pullback
                                                spring trip operating mechanism (jump mechanism) with loss of
                                                phase protection for T85 & TSA45, backpack jump mechanism
                                                for T170 & T105, main circuit with instrument transformer jump
                                                mechanism with loss of phase for T250 & T370.

         Specification:


                   Type              T16       T25      T45       T85     T105      T170     T250     T370
             Rated Current(A)         16        25       45       85       105      170       250      370
         Thermal Element Setting
             Current range(A)      0.11-17.6 0.17-32 0.28-48 6.0-100 27-115        90-200 100-400 100-500
                        Number         1NO,1NC            1NO,1NC         1NC,1NO,2NC          1NO,1NC
           Auxiliary     Rated          220V:3           220V:3、1.7        220V:3、2.5         220V:3、1.7
           Contacts    Operating        380V:2           380V:2、1.3        380V:2、1.3         380V:2、1.3
                      Current(A)        500V:1             500V:1.5        500V:1.5、0.8         500V:1.5




         TH-K TYPE THERMAL OVERLOAD RELAY


         The thermal overload relays are suitable for overload
         protection of AC motor operated on 8-bours duty or
         uninterrupted duty. The overload protected AC motor with
         frequency 50Hz, voltage up to 660V, current up to 40A.
         Several functions provided by these relays are phase-failure
         protection, temperature compensation, ON/OFF indication
         and manual/automatic reset.    The relays comply with
         IEC292-1 standard.

         Specification:


            Type       Plug In AC     Rated Current Of Thermal             Setting Current Range (A)
                        Contact              Element (A)

                                           0.24、0.35、0.5            0.2-0.28、0.28-0.42、0.4-0.6、0.55-0.85
           TH-K12     S-K10 S-K11      0.7、0.9、1.3、1.7、2.1              0.7-1.1、1-1.6、1.4-2、1.7-2.1
                      S-K12 S-K18     2.5、3.6、5、6.6、9、11             2-3、2.8-4.4、4-6、5.2-8、7-11、9-13



                      S-K20 S-K21           2.1、2.5、3.6                      1.7-2.1、2-3、2.8-4.4
           TH-K20     S-K25 S-K35          5、6.6、9、11                       4-6、5.2-8、7-11、9-13
                                        15、19、22、29、35               12-18、16-22、18-26、24-34、30-40


           TH-K60     S-K50 S-K65              42、54                             34-50、43-65
                      S-K80 S-K95


        192