Page 169 - Fimex Taiwan Ltd_Wiring Devices 2018
P. 169

MINIATURE CIRCUIT BREAKERS




                                                 JVM21 SERIES BREAKER (Merlin Gerin Type)


                                                ․  Material of Housing : High quality PA66
                                                ․  AC 230/400V ; 50/60Hz
                                                ․  Electro-Mechanical endurance : 4,000 cycles.
                                                ․  Rail Size : 35mm
                                                ․  Rated Frequency : 50/60Hz

                                                                                            6kA, CB,       RoHS  RoHS
                Model Type   Standard         Rated Current (A)       Poles (P)      Rated Voltage      Breaking
                                                                                                        Capacity
                                                                         1P
                                               1, 2, 3, 4, 6,10         1P+N
                                            13, 16, 20, 25, 32, 40A      2P
                  JVM21      IEC60898                                                 AC 230/400V          6kA
                                                                          3P
                                                  50 ,63A               3P+N
                                                                          4P

                  Test     Tripping                                                     Expected
               Procedure     type     Test Current  Initial State   Tripping Time         Result         Remark
                    A       B, C, D      1.13ln        Cold             t≦1h            No Tripping
                                                                                                     Current in the 5s
                    B       B, C, D      1.45ln     After test (A)      t<1h             Tripping    in the increase of
                                                                                                         stability
                                                                  1s<t<60s (ln≦32A)
                    C       B, C, D      2.55ln        Cold                              Tripping
                                                                 1s<t<120s (ln>32A)
                              B           3ln
                                                                                                       Turn on the
                    D         C           5ln          Cold            t≧0.1s           No Tripping  auxiliary switch to
                                                                                                     close the current
                              D           10ln
                              B           5ln
                                                                                                       Turn on the
                    E         C           10ln         Cold            t<0.1s            Tripping    auxiliary switch to
                                                                                                     close the current
                              D           20ln


                                         Tripping Characteristic Curve : B, C, D































                                                                                                                167